With regards to boiler water level control. Explain the following:
(a) Shrink and swell phenomenon (4)
(b) Cascade control (4)
(c) Split control (4)
(d) Condensing chamber – Function and location. (4)
With regards to boiler water level control. Explain the following:
(a) Shrink and swell phenomenon (4)
(b) Cascade control (4)
(c) Split control (4)
(d) Condensing chamber – Function and location. (4)
Structured for DG Shipping MEO Class II examination scoring criteria.
In split control, a single controller is used for more than one final control element making the control process more effective and at low cost.
A condensing chamber (or condensing pot) is used in boiler drum level measurement systems with differential pressure transmitters to improve accuracy at high pressure and temperature. The chamber cools and condenses steam into water within the measuring line so that the differential pressure transmitter senses hydrostatic pressure of water only (excluding steam pressure variations). It is located at the end of the impulse lines connected to the boiler drum, usually near the transmitter. The condensing chamber stabilizes the measurement by preventing steam from entering the impulse line and causing measurement errors due to temperature and density changes.