Q2 (16 Marks) Engine Operation & Maintenance
MEP • Written Exam

(a) Explain in detail how the engine room's hyper mist or high presure fog fire fighting system works in auto mode and manual mode.

(b) How you would isolate hyper mist or high pressure fog fire fighting system for routine maintenance. Describe all tests and inspections you would make and how you would return the system to service.

Appeared In: Jun 2022

Verified Model Answer (Text Solution)

Structured for DG Shipping MEO Class II examination scoring criteria.

Exam Ready

ENGINE ROOM HYPER-MIST (HIGH-PRESSURE WATER FOG) FIRE FIGHTING SYSTEM

Part (a)

How the system works in auto mode and manual mode

Auto mode:

  • The system is fitted with smoke/ heat detectors in the protected space (engine room). When a detector senses a fire (smoke/ rapid temperature rise), it sends a signal to the control panel.
  • The control panel, on confirmation (e.g. two detectors or a single detector with a time delay), automatically activates the system: it starts the high-pressure water pump(s), opens the section/ zone valves, and discharges high-pressure water through the mist nozzles in the affected zone.
  • The high-pressure water (typically 60-100 bar) is atomised into a fine mist (water fog) that fills the space, extinguishing the fire by cooling, smothering (steam generation) and blocking radiant heat.
  • The system also sounds the alarm and may shut down the ventilation/ fuel supply to the space.

Manual mode:

  • The system can be operated manually from the control panel or from manual release stations (pull stations) located at the space entrances/ on the bridge.
  • On manual activation, the operator starts the pump(s) and opens the zone valves to discharge the mist into the protected space.
  • Manual operation allows the fire to be fought selectively (e.g. a specific zone) and is used when the automatic system has not activated or when the operator decides to act.
Part (b)

Isolating the system for routine maintenance, tests, and returning to service

Isolation:

  • Inform the watch/ duty engineer and obtain permission; prepare a permit-to-work/ risk assessment.
  • Isolate the system: close the section/ zone valves, stop the pump(s), and isolate the power/ control supply to the system. Tag the system "isolated for maintenance".
  • Depressurise the system (drain the high-pressure lines) as required.
  • Ensure the protected space is safe (no fire risk) before isolating the system.

Tests and inspections:

  • Inspect the nozzles for blockage/ damage and clean/ renew as required.
  • Check the pump(s), the pressure, the control panel and the detectors for correct operation.
  • Test the alarms and the automatic/ manual activation (functional test).
  • Check the water supply/ tank level and the system pressure.
  • Test the zone valves for correct operation.

Returning to service:

  • Complete the maintenance, remove the tags/ locks, and re-energise the system.
  • Refill/ re-pressurise the system and confirm the pressure is correct.
  • Carry out a functional test (alarm, pump start, valve operation) to confirm the system is operational.
  • Record the maintenance and the test, and inform the watch/ duty engineer that the system is back in service.