Q8 (16 Marks) Engine Operation & Maintenance
MEP • Written Exam

With reference to fire pumps.

(a) Explain how and when fire pumps should be tested, what are the requirements as per SOLAS74, as amended. (6)

(b) Describe the routine maintenance to be carried out on the various fittings on a fire line, giving testing pressure where appropriate. (4)

(c) Describe briefly how will you dismantle a fire pump for survey. Give details of factors which will decide replacing the parts. (6)

Appeared In: Nov 2023

Verified Model Answer (Text Solution)

Structured for DG Shipping MEO Class II examination scoring criteria.

Exam Ready
Part (a)

TESTING OF FIRE PUMPS AND SOLAS REQUIREMENTS

How and when fire pumps should be tested:

  • Fire pumps should be tested regularly (e.g. weekly/ monthly) to confirm they operate correctly and deliver the required pressure and flow. They are tested by running the pump and checking the discharge pressure, flow, and that the pump starts/ stops correctly.
  • The pumps are also tested during drills and at survey.
  • The fire main is tested by running the fire pumps and checking the pressure at the hydrants/ nozzles.

SOLAS 74 (as amended) requirements:

  • The fire pumps must be capable of delivering the required quantity of water at the required pressure (the fire main pressure must be maintained at the hydrants).
  • The number and capacity of fire pumps are specified (e.g. at least two fire pumps, each capable of delivering the required flow; the total capacity must meet the requirements).
  • The fire pumps must be capable of being started and operated independently.
  • The fire main must be maintained at the required pressure, and the pumps must be able to deliver the required flow at the required pressure.
  • Emergency fire pump (if fitted) must be capable of delivering the required flow and pressure and be operable independently.
Part (b)

ROUTINE MAINTENANCE OF FIRE LINE FITTINGS AND TESTING PRESSURE

  • Fire hydrants, valves, hoses and nozzles are inspected and maintained regularly: check for leaks, corrosion, damage and correct operation.
  • The fire main is tested at the required pressure (e.g. the working pressure, or as per the maker/ Class - typically the fire main is tested to the working pressure, and the system is pressure-tested at survey).
  • Hoses are inspected for damage/ deterioration and pressure-tested periodically.
  • The fire pump is tested for pressure and flow.
  • The international shore connection and the fire main isolating valves are checked.
Part (c)

DISMANTLING A FIRE PUMP FOR SURVEY AND FACTORS DECIDING REPLACEMENT OF PARTS

  • Dismantling: Isolate the pump, drain it, remove the coupling/ drive, and dismantle the pump (remove the casing, impeller, shaft, bearings, seals, wear rings). Clean and inspect each part.
  • Factors deciding replacement of parts:
  • Impeller: worn, eroded, corroded, or damaged (cracked/ broken) - replace if the wear/ damage affects performance.
  • Shaft: worn, scored, bent, or corroded - replace if damaged.
  • Bearings: worn, pitted, or damaged - replace if the clearance/ condition is beyond limits.
  • Seals/ packing: worn, leaking - replace.
  • Wear rings: worn beyond the clearance limit - replace.
  • Casing: corroded, cracked, or wasted - repair or replace.
  • The decision is based on the measured wear/ damage against the maker's limits and the effect on the pump's performance and reliability.