With respect to the High Voltage power systems installation, explain the different types of circuit breaker that are used, comparing them on merits and de-merits. Describe the theory of arc phenomenon and the mechanism fitted to mitigate the arc. (16)
✓ Verified Model Answer (Text Solution)
Structured for DG Shipping MEO Class II examination scoring criteria.
Types of Circuit Breakers
1. Vacuum Circuit Breaker (VCB):
In VCBs, the fixed and moving contacts, along with the arc shield, are housed in an arc-interrupting chamber with a high vacuum. The vacuum's excellent dielectric strength allows for very short contact separation and rapid recovery of insulation strength after each interruption.
Merits:
- Compact size and quick operation due to minimal contact travel.
- Low maintenance and long operational life.
- No need for periodic refilling (unlike oil or gas CBs).
- Rapid recovery of dielectric strength.
Demerits:
- System failure is possible if there is a minor vacuum leakage.
- High cost of manufacturing.
2. SF₆ (Sulfur Hexafluoride) Gas Circuit Breaker:
These breakers utilize high-pressure SF₆ gas as an arc-extinguishing medium. The gas absorbs free electrons from the arc path, forming ions that increase the medium's dielectric strength. The gas is later recycled back to a high-pressure reservoir for reuse.
Merits:
- Excellent arc-extinguishing and insulating properties.
- Non-flammable and chemically stable.
- Does not produce toxic fumes or explosive decomposition products.
- Noiseless operation and requires minimal maintenance.
Demerits:
- SF₆ gas is a potent greenhouse gas and harmful if leaked.
- Requires a dry atmosphere; moisture can lead to operational failures.
- Suffocating gas that settles at the bottom due to its weight.
3. Oil Circuit Breaker:
When an arc forms, the surrounding oil evaporates and dissociates, producing hydrogen gas. The hydrogen displaces the oil around the arc, cools it, and provides a cooling effect to extinguish the arc.
Merits:
- The oil absorbs arc energy and provides effective cooling.
Demerits:
- Risk of fire and explosion due to the combustible nature of oil.
- Oil quality deteriorates over time, requiring periodic renewal.
4. Air Blast Circuit Breaker:
High-pressure air is introduced into the arc chamber through a nozzle when a fault occurs. The air cools the arc and sweeps away ionized particles, increasing the dielectric strength of the medium
Merits:
- Faster arc quenching and breaking speed.
- No risk of fire.
- Requires minimal maintenance.
Demerits:
- High maintenance requirements for the air compressor system.
- Possibility of air leakage from the system.
Arc Phenomenon:
When the contacts of a circuit breaker begin to separate under fault conditions, the contact area reduces rapidly. This reduction, combined with high fault current, increases the current density and causes a rise in temperature. The heat ionizes the surrounding medium, creating a conductive path for the current, which results in the formation of an arc between the breaker contacts. This arc persists as long as the ionized medium provides a low-resistance path, keeping the circuit energized.
Arc Mitigation Techniques:
- Increase the separation between the contacts to ensure that the potential difference across them is insufficient to sustain the arc.
- Use mediums like high-pressure SF₆ gas, vacuum, or air blasts to de-ionize the medium and extinguish the arc.
- Employ materials with high dielectric strength to recover insulation between contacts rapidly.