Q6 (10 Marks) Electrical Circuits & Calculations 🔥 Repeated 6x in exams
MET • Written Exam

A 72 KVA transformer supplies a heating and lighting load of 12 kW at unity power factor and a motor load of 70 kVA at 0.766 (lagging) power factor. Calculate the minimum rating of the power-factor improvement capacitors which must be connected in the circuit to ensure that the transformer does not become overloaded

Appeared In: Sep 2024Dec 2019Sep 2019Jun 2019Mar 2019Oct 2018

Verified Model Answer (Text Solution)

Structured for DG Shipping MEO Class II examination scoring criteria.

Exam Ready

A 72 kVA transformer supplies a heating and lighting load of 12 kW at unity p.f. and a motor load of 70 kVA at 0.766 p.f. lagging. Calculate the minimum capacitor rating so the transformer is not overloaded.

  • Motor: kW = 70 x 0.766 = 53.62 kW. sin phi = sqrt(1 - 0.766^2) = sqrt(0.4132) = 0.6428. Motor kVAr = 70 x 0.6428 = 45.0 kVAr (lagging).
  • Total kW = 12 + 53.62 = 65.62 kW. Total kVAr = 45.0 kVAr.
  • Present total kVA = sqrt(65.62^2 + 45^2) = sqrt(4306 + 2025) = sqrt(6331) = 79.6 kVA. This exceeds 72 kVA, so the transformer is overloaded.
  • To avoid overloading, the total kVA must be reduced to 72 kVA. The kW (65.62 kW) is fixed, so the allowable kVAr is:

kVAr = sqrt(72^2 - 65.62^2) = sqrt(5184 - 4306) = sqrt(878) = 29.6 kVAr.

  • Capacitor kVAr required = 45.0 - 29.6 = 15.4 kVAr.

So the minimum rating of the power-factor improvement capacitors is about 15.4 kVAr (say 16 kVAr).

← Back to MET Question Bank Upload Recent Question Paper →