Q6 (16 Marks) Electrical Circuits & Calculations
MET • Written Exam

(a) Describe International protection rating and types of insulation. (6)

(b) A 72 KVA transformer supplies a heating and lighting load of 12 KW at unity power factor and a motor load of 70 kVA at 0.766 (lagging) power factor: Calculate the minimum rating of the power-factor improvement capacitors which must be connected in the circuit the ensure that the transformer does not become overloaded. (10)

Appeared In: Mar 2025

Verified Model Answer (Text Solution)

Structured for DG Shipping MEO Class II examination scoring criteria.

Exam Ready

Ingress Protection (IP) Rating

Ingress Protection (IP) Rating is an internationally recognized standard defined by IEC 60529. It classifies and rates the degree of protection provided by electrical enclosures against:

  1. Solid foreign objects (dust, tools, fingers, etc.)
  2. Water/ moisture ingress

Format

The rating is expressed as IP followed by two digits:

Example: IP 56

  • First Digit (0–6): Protection against solids

Digit

Protection Description

0

No protection

1

Protection from large objects ( >50 mm )

2

Finger protection ( >12.5 mm )

3

Tools and wires protection ( >2.5 mm )

4

Small wires protection ( >1 mm )

5

Dust protected (limited ingress allowed)

6

Dust tight (no ingress permitted)

  • Second Digit (0–9): Protection against water

Digit

Protection Description

0

No protection

1

Vertical dripping water

2

Dripping water up to 15° tilt

3

Spraying water at angles up to 60°

4

Splashing water from any direction

5

Low pressure jets (all directions)

6

Powerful water jets

7

Temporary immersion in water

8

Continuous immersion in water

9K

High-pressure, high-temperature jets

Example Meaning:

  • IP 55 → Dust protected, protected against low-pressure water jets
  • IP 68 → Fully dust tight, can withstand continuous immersion

Types of Insulation

Electrical insulation prevents undesired flow of current and protects equipment and personnel from electric shock, fire hazards, and breakdowns.

A. Based on Application

Type of Insulation

Function

Primary Insulation

First level protection around current-carrying conductors

Secondary (Supplementary) Insulation

Additional protection if primary fails

Double Insulation

Combination of primary + supplementary to ensure complete safety (used in Class II equipment)

Reinforced Insulation

Single insulation with equivalent protection of double insulation

B. Based on Location in Electrical Machines

Type

Description

Slot insulation

Insulation between stator core and windings

Turn insulation

Between individual turns of a coil

Phase insulation

Between different windings/phases

Ground insulation

Between winding and earthed frame

Conductor insulation

Enamel or varnish on conductor wire

C. Based on Thermal Class (IEC 60085)

Materials are categorized by allowable operating temperature:

Class

Max Temperature

Example Materials

Class Y

90°C

Paper, cotton

Class A

105°C

Thermoplastic varnished paper

Class E

120°C

PVC

Class B

130°C

Mica, glass fiber, impregnated polyester

Class F

155°C

Silicone resin, Nomex

Class H

180°C

Silicone elastomers

Class C

>180°C

Mica, ceramic, glass (no organics)

D. Based on Environment/Installation

Type

Examples

Moisture-resistant

Rubber, PVC

Heat-resistant

Mica tapes, fiberglass

Chemical-resistant

Special polymers

Fire-retardant

Halogen-free insulation

Part (b)
← Back to MET Question Bank Upload Recent Question Paper →