Q8 (10 Marks) Electric Machines (Motors & Generators) 🔥 Repeated 2x in exams
MET • Written Exam

(a) Explain Distribution factor and Pitch factor for Alternator windings.

(b) A 3phase, 4 pole 24 slot alternator has its armature coils short pitched by one slot. Find the distribution factor and pitch factor.

Appeared In: Jan 2019Sep 2018

Verified Model Answer (Text Solution)

Structured for DG Shipping MEO Class II examination scoring criteria.

Exam Ready
Part (a)

Distribution Factor (Kd):

The distribution factor is a measure of how the EMF induced in a distributed winding compares to the EMF induced if the winding were concentrated in one slot. It is given by the formula:

$$K_{d}=\frac{EMF\:induced\:in\:distributed\:windings}{EMF\:induced\:in\:concentrated\:windings}$$

  • Concentrated Winding: All the coils of a phase under one pole are grouped in a single slot.
  • Distributed Winding: The winding is spread across multiple slots under a pole to achieve a more sinusoidal waveform and reduce harmonics.

Pitch factor (Kp):

The pitch factor accounts for the difference between the resultant EMF of short-pitched coils and the resultant EMF of full-pitched coils. It is defined as:

$$K_{p}=\frac{Resultant\:EMF\:of\:short-pitched\:coil}{Resultant\:EMF\:of\:full-pitched\:coil}$$

  • Full-Pitched Coil: The coil spans 180° electrical (one pole pitch), resulting in maximum induced EMF.
  • Short-Pitched Coil: The coil span is less than 180° electrical, reducing the EMF to minimize harmonics.