With respect to the hazardous areas of tankers:
(a) Explain the term flameproof (Ex d) for electrical equipment.
(b) State the type of electrical equipment that would be protected in this way.
(c) List likely defects of flameproof equipment.
With respect to the hazardous areas of tankers:
(a) Explain the term flameproof (Ex d) for electrical equipment.
(b) State the type of electrical equipment that would be protected in this way.
(c) List likely defects of flameproof equipment.
Structured for DG Shipping MEO Class II examination scoring criteria.
The most common form of hazardous area electrical equipment is the flameproof enclosure type (Ex d). The internal apparatus may include components that arc or have surfaces that become hot. Gas may also be present inside the enclosure, so it must fulfill the following three conditions:
Flame and hot gas transmission from a flameproof enclosure is prevented because all jointsâsuch as flanges, spigots, shafts, and boresâare closely machined to achieve a small gap, which is less than a defined maximum. When an internal explosion occurs, the pressure is released through this narrow gap between machined faces, which cools the gas sufficiently to prevent ignition of the external flammable atmosphere.
The maximum allowable gap depends on three factors: