Q4 (10 Marks) Fire Protection & Detection
SSEP • Written Exam

(a) What are the general requirements of fixed gas fire-extinguishing systems for shipboard use?

(b) What are the specific requirements related to CO2 systems with respect to quantity, piping, controls and volume of free CO2 What are the maintenance carried out on the Fixed co2 firefighting system.

Appeared In: Nov 2022

Verified Model Answer (Text Solution)

Structured for DG Shipping MEO Class II examination scoring criteria.

Exam Ready
Part (a)

What are the general requirements of fixed gas fire-extinguishing systems for shipboard use?

Part (b)

What are the specific requirements related to CO2 systems with respect to quantity, piping, controls and volume of free CO2? What are the maintenance carried out on the Fixed CO2 firefighting system.

(Refer to the detailed answer for 68d3d1916afe1c7ad70ac91e.)

Part (a)

General requirements of fixed gas fire-extinguishing systems (SOLAS Ch. II-2 Reg 10.4 and FSS Code):

  • The system must be suitable for the protected space (machinery spaces, cargo spaces, pump rooms, electrical spaces) and use an approved extinguishing medium (CO2, inert gas, or a clean agent).
  • The quantity of the extinguishing medium must be sufficient to extinguish a fire in the largest protected space (e.g. CO2 at the required percentage of the gross volume).
  • The system must be capable of being discharged quickly (e.g. at least 85% of the CO2 within 2 minutes) and distributed uniformly through the space.
  • The controls must be arranged so that the system cannot be discharged accidentally, and so that personnel are warned (an alarm) before discharge; the controls are located outside the protected space.
  • The system must be installed so that the protected space can be sealed (ventilation, skylights, doors closed) to retain the gas.
  • The system must be tested, maintained and the crew trained in its use.
  • The storage of the gas (cylinders) must be outside the protected space, in a suitable location, protected from heat.
Part (b)

Specific requirements for CO2 systems:

  • Quantity: For machinery spaces, the quantity of free CO2 must be at least 40% of the gross volume of the space (for spaces up to 2000 m3) and 35% of the gross volume for larger spaces (plus the casing), or as specified by the FSS Code; for cargo spaces, at least 30% of the gross volume. At least 85% of the required quantity must be discharged within 2 minutes.
  • Piping: The distribution piping must be of suitable size and material, run into the protected space with nozzles arranged to distribute the gas uniformly (nozzles near the top and a pair near the bilge/bottom); the piping is pressure-tested (e.g. 1.5x working pressure) and has no dead-ends.
  • Controls: Two independent controls (a main control and a section/quick-release valve), arranged so that a person can operate the system; the controls are located outside the protected space (a release cabinet), with a two-stage operation (first an alarm, then the discharge); a pressure gauge, safety/relief valve, and non-return valves are fitted.
  • Volume of free CO2: The "free CO2" is the volume of CO2 gas that would be produced from the liquid CO2 in the cylinders; the quantity is calculated to give the required percentage of the gross volume of the protected space.
  • Maintenance: Weekly/monthly checks of the cylinder pressures and leak tests, valve operation, alarm tests, piping/nozzle inspection; periodic (e.g. 5-yearly or per the approved schedule) discharge/test and hydrostatic test of the cylinders; inspection of the release mechanism; and the system is serviced by an approved station. All tests are recorded.