Q6 (10 Marks) Fire Protection & Detection 🔥 Repeated 2x in exams
SSEP • Written Exam

State the regular routines carried out on the following system:

(a) Self contained Breathing apparatus (SCBA).

(b) Accommodation Fixed Fire detection system.

Appeared In: Jul 2025Aug 2019

Verified Model Answer (Text Solution)

Structured for DG Shipping MEO Class II examination scoring criteria.

Exam Ready
Part (a)

The following are the routine test required for self contained breathing apparatus sets:

Backplate and harness:

  • Check that the backplate is in good condition and free of damage and excess wear.
  • Check that the harness is clean and free of damage. Also check it slides freely through buckles.

Pneumatics:

  • Check cylinder connector o-ring is cleaned and undamaged.
  • Screw hand wheel connector firmly into the cylinder valve outlet.
  • Check that pressure gauge, whistle and hoses are in good condition and are not stretched.

Check Demand Valve:

  • Check that the demand valve o-ring is clean and undamaged.
  • Fit the demand valve to the face-mask. Check that the locking catch clicks into place.

Check Face-mask:

  • Check that the face-mask is clean and undamaged and check if vision is clear.
  • Place chin in face-mask chin cup and pull the head harness over the head.
  • Tightened head harness in sequence bottom – middle – top.
  • Open the cylinder valve and check that the cylinder is full.
  • Check that the face-mask pressurises. If necessary, adjust the mask to obtain a leak tight fit.
  • Do not over tightened the harness as it distorts the mask.

Pressure and leak test:

  • Insert fingers in the face-mask seal and check there is steady flow of air out of the mask. Remove fingers and allow mask to reseal.
  • Close the cylinder valve, hold your breath and monitor the pressure gauge for 10 sec. Check that the pressure does not change during the period.

Whistle Test:

  • Monitor the pressure gauge, breath down air in the system and check that the whistle sounds clearly between 50 and 60 bars.
  • Release head harness and remove face-mask.

Final checks:

  • Check that all parts are clean and undamaged.
  • Ensure that the shoulder harness is fully slackened and that a full cylinder is securely attached.
  • Replace discharged cylinder.
  • If any check fails, attach an explanatory note to apparatus and return it to be serviced.