What risk occurs if a generator breaker is closed out of phase (e.g. 180° out of phase) with live HV busbar?

✓

Direct Answer

Option B: Severe mechanical torque shock shearing generator shaft, massive fault current, and switchboard explosion

Closing a breaker 180° out of phase creates a massive potential difference, causing instantaneous fault currents that exceed the mechanical design limits of the generator shaft and switchgear. This catastrophic event leads to severe torque shock, potential shaft shearing, and explosive arc flash incidents, violating fundamental synchronization safety protocols defined in IEC 60092-503.

All Options

A
Engine stops
B
Severe mechanical torque shock shearing generator shaft, massive fault current, and switchboard explosion (Correct Answer)
C
Slight light dim
D
Smooth speed up

Detailed Explanation & Context

Closing a breaker 180° out of phase creates a massive potential difference, causing instantaneous fault currents that exceed the mechanical design limits of the generator shaft and switchgear. This catastrophic event leads to severe torque shock, potential shaft shearing, and explosive arc flash incidents, violating fundamental synchronization safety protocols defined in IEC 60092-503.

Relevant Framework: STCW 2010 Manila Amendments • DG Shipping E-Learning & Exit Exam Standards • High Voltage Safety Officer & Switchgear Operations (HV).

Advertisement

Practice Full HV Set 2

Test yourself with 30 interactive questions, live timer, and instant score.

Launch Practice Simulator →

Question Discussion & Notes

0

Have a doubt, memory trick, or exam update? Share your insights with fellow mariners.

Leave a Comment / Clarification

By posting, you agree to our Terms & Moderation Policy.

Loading mariner discussions...